Home › Products › Cable Accessories › 600A Deadbreak (15/25kV) › Description
| Electrical Ratings MEET OR EXCEEDS IEEE STANDARD 386-latest revision |
|
|---|---|
| Continuous Current Rating (Aluminum Components) |
600 amps |
| Voltage Class | 25kV |
| Max Phase to Ground Voltage - Operating Voltage |
15.2kV |
| Max Phase to Phase | 26.3kV |
| Basic Impulse Level (1.2x50μs) |
125kV |
| Corona Extinction (3pC) |
19kV |
| AC Withstand Voltage (1 min.) |
40kV |
| DC Withstand Voltage (15 min.) |
78kV |
| 24 Hour Overload | 1,000 A rms |
| Short Time | 25,000 A rms symmetrical for 0.17 sec. 10,000 A rms symmetrical for 3.00 sec. |
| 100% Production Test | |
| Corona (3pC) | 19kV |
| AC Withstand (1 min.) | 40kV |
The Hubbell 600 amp Deadbreak Elbow and accessories offer an easy and reliable method of terminating and splicing main feeder circuits. The Deadbreak Elbow is a fully shielded, molded rubber connector.
The Deadbreak Elbow is designed to terminate power cables with copper or aluminum conductors ranging in sizes from #2 AWG to 1250 kcmil. It may be installed on any 600 amp rated (aluminum) apparatus bushing that meets IEEE Standard 386 latest revision for Separable Insulated Connectors. Cable adapters accommodate power cable insulation diameters from 0.530 to 1.935 inches.
The Hubbell Deadbreak Elbow has been designed and tested to meet the requirement of IEEE Standard 386. Conformance to this industry standard ensures mechanical and electrical interchangeability with other products of manufacturers that are also in conformance with the standard.
|
|